They are active air/water continuous chillers for accurate temperature control (+/- 0.1 °C) for installation in standardized 19″ rack systems.
ATC is the UK’s leading manufacturer of recirculating chillers and temperature control products. From standard products to fully customized systems, ATC can offer you the best cooling solution and temperature control for your problems.
What makes the device special:
Use for cooling / temperature control of:
R05 | R10 | R20 | |
---|---|---|---|
Cooling capacity (1) | 500 Watt | 1.150 Watt | 1.900 Watt |
Temperature range (standard) | + 4 °C to + 35°C | ||
Temperature range (optional) | -5 °C to +65 °C | ||
Temperatur stability at constant load | +/- 0.1 °C | ||
Principle | compression chiller | active air / water chiller | also as water/water chiller available | ||
Pump options and flow rates at 6 bar back pressure | 3.8 l/min at 1 bar (cerntrifugal pump) | 4 l/min at 4 bar (PD pump) | |
System volume | 2.8 l | 4 l | 7.5 l |
Compatibility | Hexid, propylene-glycol, dest. water | ||
Operating pressure range | currently unkown |
1 Performance at 30°C ambient temperature at the chiller and 20°C setpoint for application to be cooled
R05 | R10 | R20 | |
---|---|---|---|
Weight | 25 kg | 36 kg | 48 kg |
Size (L x W x H) | 19″ rack 5U height 500 mm depth | ||
Noise level | 35 – 64 dB (A) | 63 dB (A) | |
F-gas amount (2) / type, GWP (1) and CO2 equivalent | 0.36 kg R134a (GWP 1430) 0.52 t CO2 | 0.5 kg R134a (GWP 1430) 0.72 t CO2 | 0.66 kg R407C (GWP 1774) 1.17 t CO2 |
Operating voltage and maximum power requirement / for 50 Hz | 230V – 2.8 A | 230V – 6.5 A | 230V – 7.5 A |
Environmental temperature | + 15 °C to + 40 °C | ||
Min. inside diameter of pipeline | 12 mm |
1GWP: Global warming potential – the global warming potential that this refrigerant has compared to CO2 over a period of 100 years
2 Specification for standard air / water cooling variant
Manuals for download:
Brochures and other information for download: