Passive cooler: water/water XF series from ATC – cooling capacity: 4.000 – 25.000 W

They are passive water / water coolers (without cooling system and refrigerant) for cooling process fluids. Cooling is carried out purely by temperature difference between medium and cooling water.

ATC is the UK’s leading manufacturer of recirculating chillers and temperature control products. From standard products to fully customized systems, ATC can offer you the best cooling solution and temperature control for your problems.

What distinguishes it:

  • Cost-effective operation
  • Separation of cooling water from medium to be cooled (e.g. hygienic reasons).
  • Heat exchangers are available in different configurations (aluminum, stainless steel, titanium)
  • Different medium temperatures for different processes can be achieved with the same cooling water.
  • A very wide range of different pump configurations possible (more than indicated in the table) – with differences in pulsation and flow rate.
 

Use for cooling / temperature control of:

  • Laser systems
  • X-ray sources
  • Vacuum pumps
  • Resistance welding machines
  • High-frequency generators
  • Ovens
  • Hydraulic systems
  • RF generators
  • Additive manufacturing
  • Cooling of cryocompressors
  • Plasma etching
  • Deposition systems
  • Microchip  production
  • Extruders

Relevant performance specifications

XF04XF15XF25
Cooling capacity (1)4.000 Watt15.000 Watt25.000 Watt
Temperature range (standard)+ 4 °C to + 55°C+ 4 °C to + 70°C
Temperature range (optional)+ 4 °C to + 90°C
Temperatur stability at constant load+/- 0.1 °C
Principlepassive water/water cooler
Pump options and flow rates at 6 bar back pressureP5 – 5 l/minP17 – 17 l/min
P25 – 25 l/min
P25 – 25 l/min
System volume2.3 l2.3 l11 – 15 l
CompatibilityHexid, dest. water, propylene-glycol
Operating pressure range1 – 10 bar

1 return line 10 °C above cooling water temperature

Other relevant specifications

XF04XF15XF25
Weight40 kg80 kg
Size (L x W x H)545 x 420 x 575mm413 x 473 x 819mm (1)775 x 510 x 850mm
Noise level50 dB (A) 1 m
Operating voltage and maximum power requirement / for 50 Hz230 V – 3 A230 V – 4 A230 V – 4.5 A
Environmental temperature+ 4 °C to + 40 °C
Min. inside diameter of pipeline12 mm

1 for 17 L/min pump option