Passive cooler: Airblast Coolers A01 – A03 from ATC – Cooling capacity: 1.000 – 3.000 W

They are passive air/water chillers (without cooling system and refrigerant) for cooling process fluids. The cooling takes place purely by temperature difference between medium and ambient temperature.

ATC is the UK’s leading manufacturer of recirculating chillers and temperature control products. From standard products to fully customized systems, ATC can offer you the best cooling solution and temperature control for your problems.

What makes the device special:

  • Cost-effective operation
  • Can also be used in combination with other coolers. Example: one or more active coolers as an indoor water/water option and an Airblast cooler outdoor. As a result, the heat is efficiently dissipated directly into the outdoor area without burdening the air conditioning system. Furthermore, the noise pollution in the interior is reduced, since no evaporator fan is required indoor.
 

Use for cooling / temperature control of:

  • Inverter
  • Welding torches
  • Hydrogen electrolysis
  • Uniaxial press machinery
  • Stamping machines
  • Cooling electronics
  • Material testing
  • Devices for cancer therapy
  • Climate chambers
  • RF generation
  • Testing of engines
  • Roots blowers
  • Cooling of furnaces
  • Asphalt screening
  • Large motors for mixing plants

Relevant performance specifications

A01A03
Cooling capacity (1)1.000 Watt3.000 Watt
Max. temperature return line (standard)+ 60 °C
Max. temperature return line (option)+ 85 °C
Temperatur stability at constant loadcurrently unknown+/- 0.5 °C
Principlepassive air / water chiller | only indoor installationpassive air / water chiller | indoor and outdoor installation possible
Pump options and flow rates at 6 bar back pressurePC3 – 1.3 l/min
PC6 – flowrate currently unkown
P5 – 5 l/min
P10 – 10 l/min
P17 – 17 l/min
System volume1 l5 l
CompatibilityHexid, Propylene-Glycol, water
Operating pressure range (2)currently unkownup to 10 bar

1 At ambient temperature 10 °C higher than the return temperature of the Airblast Cooler and additional 10 °C heating by the application to be cooled

2 Specified presure ranges only applies to PD pumps and not to centrifugal pumps

Other relevant specifications

A01A03
Weight10 kg65 kg
Size (L x W x H)435 x 180 x 380 mm540 x 550 x 713 mm
Noise level54 dB (A) 1 m65 dB (A) 1 m
Operating voltage and maximum power requirement / for 50 Hz230 V – 1 A230 V – 4 A
Environmental temperatureup to + 40 °Cup to + 50 °C
Min. inside diameter of pipeline12 mm