They are passive water / water continuous chillers (without cooling system and refrigerant) for installation in standardized 19″ rack systems. Cooling is carried out purely by temperature difference between medium and cooling water.
ATC is the UK’s leading manufacturer of recirculating chillers and temperature control products. From standard products to fully customized systems, ATC can offer you the best cooling solution and temperature control for your problems.
What makes the device special:
- Cost-effective operation
- Separation of cooling water from medium to be cooled (e.g. hygienic reasons).
- Different medium temperatures for different processes can be achieved with several coolers but the same cooling water.
Use for cooling / temperature control of:
- Resistance welding machines
- RF Generators
- Ovens
- X-ray equipment
- Laser
- General process cooling
Relevant performance specifications
XR04 | XR08 | XR15 | |
Cooling capacity1 | 4.000 Watt | 8.000 Watt | 15.000 Watt |
Temperature range2 (standard) | + 4 °C to + 55°C | + 4 °C to + 55°C | + 4 °C to + 55°C |
Temperatur stability at constant load | +/- 0.1 °C | +/- 0.1 °C | +/- 0.1 °C |
Principle | passive water/water cooler | passive water/water cooler | passive water/water cooler |
Pump options and flow rates at 6 bar back pressure | P5 – 5 l/min | P10 – 10 l/min | P17 – 17 l/min |
System volume | 2.3 l | 2.3 l | 2.3 l |
Compatibility | Hexid, dest. water, propylene-glykol | Hexid, dest. water, propylene-glykol | Hexid, dest. water, propylene-glykol |
Operating pressure range | 1 – 10 bar | 1 – 10 bar | 1 – 10 bar |
1 Return line 10 °C above cooling water
2 Additional furher temperature ranges are available
Other relevant specifications
| XR04 | XR08 | XR15 |
Weight | 30 kg | 30 kg | 30 kg |
Size (L x W x H) | 19″ rack 5 U height 500 mm depth | 19″ rack 5 U height 500 mm depth | 19″ rack 5 U height 500 mm depth |
Noise level | 45 dB (A) 1 m | 45 dB (A) 1 m | 45 dB (A) 1 m |
Operating voltage and maximum power requirement / for 50 Hz | 230 V – 3 A | 230 V – 3 A | 230 V – 4 A |
Environmental temperature | -20 °C to + 40 °C | -20 °C to + 40 °C | -20 °C to + 40 °C |
Min. inside diameter of pipeline | 12 mm | 12 mm | 12 mm |