Recirculating chiller: 19″ rack desgin R-series from ATC – cooling capacity: 500 – 1.900 Watt

They are active air/water continuous chillers for accurate temperature control (+/- 0.1 °C) for installation in standardized 19″ rack systems.

ATC is the UK’s leading manufacturer of recirculating chillers and temperature control products. From standard products to fully customized systems, ATC can offer you the best cooling solution and temperature control for your problems.

What makes the device special:

  • Suitable for standard housings for electrical components with a minimum internal depth of 23.62 inches or 600 mm
  • Space saving cooling with an output of 0.5 – 2 kW possible
  • By connection to a cooling water circuit, it can also be used as a water / water cooler (corresponding chiller configuration required)
  • Due to the stainless steel design of the evaporator and the coolant tank, it can also be used for corrosion-free environmental conditions.

Use for cooling / temperature control of:

  • Laser Sources
  • RF Signal Generators
  • Röngtenquellen
  • Optical Devices
  • 3D printing
  • Ozondesinfektion
  • Elektronenmikroskope

Relevant performance specifications

R05R10R20
Cooling capacity1500 Watt1.150 Watt1.900 Watt
Temperature range
(standard)
+ 4 °C to + 35°C+ 4 °C to + 35°C+ 4 °C to + 35°C
Temperature range
(optional)
– 5 °C to + 65°C– 5 °C to + 65°C– 5 °C to + 65°C
Temperatur
stability at constant load
+/- 0.1 °C+/- 0.1 °C+/- 0.1 °C
Principlecompression chiller

active air / water chiller

also as water/water chiller available
compression chiller

active air / water chiller

also as water/water chiller available
compression chiller

active air / water chiller

also as water/water chiller available
Pump options and flow rates at 6 bar back pressure
3.8 l/min at 1 bar
(cerntrifugal pump)
4 l/min at 4 bar
(PD pump)
4 l/min at 4 bar
(PD pump)
System volume2.8 l4 l7.5 l
CompatibilityHexid, propylene-glycol, dest. waterHexid, propylene-glycol, dest. waterHexid, propylene-glycol, dest. water
Operating pressure rangecurrently unkowncurrently unkowncurrently unkown

1 Performance at 30°C ambient temperature at the chiller and 20°C setpoint for application to be cooled

Other relevant specifications

R05R10R20
Weight25 kg36 kg48 kg
Size19″ rack
5U height
500 mm depth
19″ rack
5U height
500 mm depth
19″ rack
5U height
500 mm depth
Noise level35 – 64 dB (A)63 dB (A)63 dB (A)
F-gas amount2 /
type, GWP1 and
CO2 equivalent
0.36 kg R134a
(GWP 1430)
0.52 t CO2
0.5 kg R134a
(GWP 1430)
0.72 t CO2
0.66 kg R407C
(GWP 1774)
1.17 t CO2
Operating voltage and
maximum power
requirement / for 50 Hz
230V – 2.8 A230V – 6.5 A230V – 7.5 A
Environmental
temperature
+ 15 °C to + 40 °C+ 15 °C to + 40 °C+ 15 °C to + 40 °C
Min. inside diameter
of pipeline
12 mm12 mm12 mm

1GWP: Global warming potential – the global warming potential that this refrigerant has compared to CO2 over a period of 100 years

2 Specification for standard air / water cooling variant

Manuals for download:

Brochures and other information for download: