They are passive water / water coolers (without cooling system and refrigerant) for cooling process fluids. Cooling is carried out purely by temperature difference between medium and cooling water.
ATC is the UK’s leading manufacturer of recirculating chillers and temperature control products. From standard products to fully customized systems, ATC can offer you the best cooling solution and temperature control for your problems.
What distinguishes it:
- Cost-effective operation
- Separation of cooling water from medium to be cooled (e.g. hygienic reasons).
- Heat exchangers are available in different configurations (aluminum, stainless steel, titanium)
- Different medium temperatures for different processes can be achieved with the same cooling water.
- A very wide range of different pump configurations possible (more than indicated in the table) – with differences in pulsation and flow rate.
Use for cooling / temperature control of:
- Laser systems
- X-ray sources
- Vacuum pumps
- Resistance welding machines
- High-frequency generators
- Ovens
- Hydraulic systems
- RF generators
- Additive manufacturing
- Cooling of cryocompressors
- Plasma etching
- Deposition systems
- Microchip production
- Extruders
Relevant performance specifications
XF04 | XF15 | XF25 | |
Cooling capacity1 | 4.000 Watt | 15.000 Watt | 25.000 Watt |
Temperature range (standard) | + 4 °C to + 55°C | + 4 °C to + 55°C | + 4 °C to + 70°C |
Temperature range (optional) | + 4 °C to + 90°C | + 4 °C to + 90°C | + 4 °C to + 90°C |
Temperatur stability at constant load | +/- 0.1 °C | +/- 0.1 °C | +/- 0.1 °C |
Principle | passive water/water cooler | passive water/water cooler | passive water/water cooler |
Pump options and flow rates at 6 bar back pressure | P5 – 5 l/min | P17 – 17 l/min P25 – 25 l/min | P25 – 25 l/min |
System volume | 2.3 l | 2.3 l | 11 – 15 l |
Compatibility | Hexid, dest. water, propylene-glycol | Hexid, dest. water, propylene-glycol | Hexid, dest. water, propylene-glycol |
Operating pressure range | 1 – 10 bar | 1 – 10 bar | 1 – 10 bar |
1 return line 10 °C above cooling water temperature
Other relevant specifications
| XF04 | XF15 | XF25 |
Weight | 40 kg | 40 kg | 80 kg |
Size (L x W x H) | 545 x 420 x 575mm | 413 x 473 x 819mm 1 | 775 x 510 x 850mm |
Noise level | 50 dB (A) 1 m | 50 dB (A) 1 m | 50 dB (A) 1 m |
Operating voltage and maximum power requirement / for 50 Hz | 230 V – 3 A | 230 V – 4 A | 230 V – 4.5 A |
Environmental temperature | + 4 °C to + 40 °C | + 4 °C to + 40 °C | + 4 °C to + 40 °C |
Min. inside diameter of pipeline | 12 mm | 12 mm | 19 mm |
1 for 17 L/min pump option
Manuals for Download:
Brochures and other information for download:
Inquiries regarding offer and advice please contact office@labsupport.at